Design of Ventilation Systems (2024)

The procedure below can be used to design ventilation systems:

  • Calculate heat or cooling load, including sensible and latent heat
  • Calculate necessary air shifts according the number of occupants and their activity or any other special process in the rooms
  • Calculate air supply temperature
  • Calculate circulated mass of air
  • Calculate temperature loss in ducts
  • Calculate the outputs of components - heaters, coolers, washers, humidifiers
  • Calculate boiler or heater size
  • Design and calculate the duct system

1. Calculate Heat and Cooling Loads

Calculate heat and cooling loads by

  • Calculating indoor heat or cooling loads
  • Calculating surrounding heat or cooling loads

2. Calculate Air Shifts according the Occupants or any Processes

Calculate the pollution created by persons and their activity and processes.

3. Calculate Air Supply Temperature

Calculate air supply temperature. Common guidelines:

  • For heating, 38 - 50 o C (100 - 120 o F) may be suitable
  • For cooling where the inlets are near occupied zones , 6 - 8 o C (10 - 15 o F) below room temperaturemay be suitable
  • For cooling where high velocity diffusing jets are used, 17 o C (30 o F) below room temperaturemay be suitable

4. Calculate Air Quantity

Air Heating

If air is used for heating, the needed air flow rate may be expressed as

q h = H h / (ρ c p (t s - t r )) (1)

where

q h = volume of air for heating (m 3 /s)

H h = heat load (W)

c p = specific heat air (J/kg K)

t s = supply temperature ( o C)

t r = room temperature ( o C)

ρ = density of air (kg/m 3 )

Air Cooling

If air is used for cooling, the needed air flow rate may be expressed as

q c = H c / (ρ c p (t o - t r )) (2)

where

q c = volume of air for cooling (m 3 /s)

H c = cooling load (W)

t o = outlet temperature ( o C) where t o = t r if the air in the room is mixed

Example - Heating Load

If the heat load is H h = 400 W , supply temperature t s = 30 o C and the room temperature t r = 22 o C , the air flow rate can be calculated as:

q h = (400 W) / ((1.2 kg/m 3 ) (1005 J/kg K) ((30 o C) - (22 o C)))

= 0.041 m 3 /s

= 149 m 3 /h

Moisture

Humidifying

If the outside air is more humid than the indoor air - then the indoor air can be humidified by supplying air from the outside. The amount of supply air can be calculated as

q mh = Q h / (ρ (x 1 - x 2 )) (3)

where

q mh = volume of air for humidifying (m 3 /s)

Q h = moisture to be supplied (kg/s)

ρ = density of air (kg/m 3 )

x 2 = humidity of room air (kg/kg)

x 1 = humidity of supply air (kg/kg)

Dehumidifying

If the outside air is less humid than the indoor air - then the indoor air can be dehumidified by supplying air from the outside. The amount of supply air can be calculated as

q md = Q d / (ρ (x 2 - x 1 )) (4)

where

q md = volume of air for dehumidifying (m 3 /s)

Q d = moisture to be dehumidified (kg/s)

Example - Humidifying

If added moisture Q h = 0.003 kg/s , room humidity x 1 = 0.001 kg/kg and supply air humidity x 2 = 0.008 kg/kg , the amount of air can expressed as:

q mh = (0.003 kg/s) / ((1.2 kg/m 3 ) ((0.008 kg/kg)- (0.001 kg/kg)))

= 0.36 m 3 /s

Alternatively the air quantity is determined by the requirements of occupants or processes.

5. Temperature Loss in Ducts

The heat loss from a duct can be calculated as

H = A k ((t 1 + t 2 ) / 2 - t r ) (5)

where

H = heat loss (W)

A = area of duct walls (m 2 )

t 1 = initial temperature in duct ( o C)

t 2 = final temperature in duct ( o C)

k = heat loss coefficient of duct walls (W/m 2 K) (5.68 W/m 2 K for sheet metal ducts, 2.3 W/m 2 K for insulated ducts)

t r = surrounding room temperature ( o C)

The heat loss in the air flow can be expressed as

H = 1000 q c p (t 1 - t 2 ) (5b)

where

q = mass of air flowing (kg/s)

c p = specific heat air (kJ/kg K)

(5) and (5b) can be combined to

H = A k ((t 1 + t 2 ) / 2 - t r )) = 1000 q c p (t 1 - t 2 ) (5c)

Note that for larger temperature drops logarithmic mean temperatures should be used.

6. Selecting Heaters, Washers, Humidifiers and Coolers

Units as heaters, filters etc. must on basis of of air quantity and capacity be selected from manufacture catalogs.

7. Boiler

Boiler rating can be expressed as

B = H (1 + x) (6)

where

B = boiler rating (kW)

H = total heat load of all heater units in system (kW)

x = margin for heating up the system, it is common to use values 0.1 to 0.2

Boiler with correct rating must be selected from manufacture catalogs.

8. Sizing Ducts

Air speed in a duct can be expressed as:

v = Q / A (7)

where

v = air velocity (m/s)

Q = air volume (m 3 /s)

A = cross section of duct (m 2 )

Overall pressure loss in ducts can be calculated as

dp t = dp f + dp s + dp c (8)

where

dp t = total pressure loss in system (Pa, N/m 2 )

dp f = major pressure loss in ducts due to friction (Pa, N/m 2 )

dp s = minor pressure loss in fittings, bends etc. (Pa, N/m 2 )

dp c = minor pressure loss in components as filters, heaters etc. (Pa, N/m 2 )

Major pressure loss in ducts due to friction can be calculated as

dp f = R l (9)

where

R = duct friction resistance per unit length (Pa, N/m 2 per m duct)

l = length of duct (m)

Duct friction resistance per unit length can be calculated as

R = λ / d h (ρ v 2 / 2) (10)

where

R = pressure loss (Pa, N/m 2 )

λ = friction coefficient

d h = hydraulic diameter (m)

Design of Ventilation Systems (2024)

References

Top Articles
Latest Posts
Article information

Author: Nicola Considine CPA

Last Updated:

Views: 5960

Rating: 4.9 / 5 (69 voted)

Reviews: 84% of readers found this page helpful

Author information

Name: Nicola Considine CPA

Birthday: 1993-02-26

Address: 3809 Clinton Inlet, East Aleisha, UT 46318-2392

Phone: +2681424145499

Job: Government Technician

Hobby: Calligraphy, Lego building, Worldbuilding, Shooting, Bird watching, Shopping, Cooking

Introduction: My name is Nicola Considine CPA, I am a determined, witty, powerful, brainy, open, smiling, proud person who loves writing and wants to share my knowledge and understanding with you.